Annual Inspection (wet type) include:
Water flow alarm tests using the inspector’s test connection to be
conducted annually (BC Fire Code Section 6.5.3.2-1))
.
Main drain water
flow test (BC Fire Code Section 6.5.3.11-1)
.
Annual inspections must also include:
General overview of system to look for proper installation and any apparent changes, alterations, additions, damage.
Operation/condition of all valves, gauges, piping, bracing, sprinklers, mechanical and electrical alarms, pumps and all other associated hardware.
Monthly Inspections include:
Inspection of water supply valves that are locked in the open position
Annual Inspections (dry type) include:
Trip test annually with control
valve partially open ( BC Fire Code Section 6.5.3.12-1 )
. (Full trip conducted through inspector’s test valve, with control valve open, must be conducted every three years.)
Auxiliary low point drains to be drained before
each winter ( BC Fire Code Section 6.5.4.8-1)
.
Most Visited
Careers
About Us
Testimonials
Fire Plans
Newsletter
Free Evaluation
Bulletins
Stop Drop and Roll
If your clothes catch fire, don't run. Stop where you are, drop to the ground, cover your face with your hands, and roll over and over to smother the flames.
Copyright 2010 - Vancouver Fire & Security Ltd. All rights reserved.
National Fire & Safety Planners
-
Vancouver Fire & Security Ltd.
. -
Radius Security